AUTOMATIC FIRE PUMP PRIMING SYSTEM
A Trident Model #31.011.1 automatic air operated priming system shall be installed. The unit shall be of all brass and stainless steel construction and designed for fire pumps of 1,250 GPM (4,690 LPM) or more. Due to corrosion exposure no aluminum or vanes shall be used in the primer design. The primer shall be three-barrel design with direct connection to the Hale fire pump. The primer shall automatically drain when the panel control actuator is not in operation. The connection to the pump shall have an integral Hale strainer.
Performance, Safety, and NFPA Compliance
The priming system shall be capable to a vertical lift to 22 inches of mercury and shall be fully compliant to applicable NFPA standards for vertical lift. The system shall create vacuum by using air from the chassis air brake system through a three-barrel multi-stage internal “venturi nozzles” within the primer body. The noise level during operation of the primer shall not exceed 75 Db.
Air Flow Requirements
The primer shall require a minimum of 15.6 cubic foot per minute air compressor and shall be capable of meeting drafting requirements at high idle engine speed. The air supply shall be from a chassis supplied ‘protected’ air storage tank with a pressure protection valve. The air supply line shall have a pressure protection valve set between 70 to 80 PSIG.
Automatic Primer Control with Vacuum Gauge
The 24 volt primer control shall be an “automatic” type, with a pump panel three-way switch to operate an air solenoid valve. The air valve shall direct air pressure from the air brake system to the primer. To prevent freezing, no water shall enter the primer valve control.
A vacuum gauge 2” in diameter, with graduations from zero to 30 feet, shall be installed in the primer control panel. The gauge shall be physically connected to the vacuum side of the primer and read only when the primer is running so it will never see or be subject to damage from high pump intake pressures.
The automatic priming switch shall have three positions as follows:
Power Requirements
To reduce the electrical power requirements on the fire apparatus the priming system shall be air powered. The system shall not require annual tear-down and maintenance, an electric motor, lubrication, belt drive, or clutch assembly. The maximum current draw shall not exceed 0.5 amps during operation.
Warranty
The primer shall be covered by a five (5) year parts warranty.